0

Your Cart

0
Subtotal: AUD0
No products in the cart.

Earthing System Types Explained

Low voltage and high voltage earthing arrangements explained and compared
Aerial of Industrial Installation with Substation 1170x585 - Earthing System Types Explained

Table of Contents

Earthing Systems Explained

An earthing system (IEC) or grounding system (IEEE) connects an electrical power system with the earth’s surface, for both safety and functional purposes. Earthing systems also affect electromagnetic compatibility and are required for lightning protection systems.

Earthing systems fall under two categories: system grounding and equipment grounding.

System grounding is the deliberate connection to earth of a phase or neutral conductor to control voltage stress and voltage hazards (touch or step voltages) to within safe limits.

Equipment grounding is to electrically interconnect or to ‘bond’ the non-current carrying conductive parts of equipment together and to the earth.

Earthing systems must be carefully designed. There are many earthing and grounding system related standards the designer needs to consider.

Low voltage earthing systems

IEC terminology

IEC terminology from the IEC 60364-1 standard [2].

First Letter – Relationship of the power system to the earth:

  • T = direct connection of one point to earth.
  • I = all live parts isolated from earth, or one point connected to earth via a high impedance.

Second letter – Relationship of the exposed-conductive-parts (ECPs) of the installation to earth:

  • T = direct electrical connection of ECPs to earth, independently of the earthing of any point of the power system.
  • N = direct electrical connection of the ECPs to the earthed point of the power system (in AC systems, the earthed point of the power system is normally the neutral point or, if a neutral point is not available, a line conductor).

Subsequent letter(s) (if any) – Arrangement of neutral and protective earthing conductors:

  • S = protective earthing function provided by a conductor separate from the neutral conductor or from the earthed line (or, in AC systems, earthed phase) conductor.
  • C = neutral and protective earthing function encapsulated into a single conductor (the PEN conductor).

TN Systems

TN, or Terre-Neutral, systems are electrical systems where the Exposed Conductive Parts (ECPs) are directly connected to a solidly grounded point of the source [1]. TN systems have low fault loop impedances but carry a higher risk of damage to the neutral (with even a risk of fire) due to higher fault currents. Additionally, earth electrodes need to be installed at regular intervals (connected to each conductor in the system) to avoid safety issues.

 TN Systems can be sorted into multiple different types, depending on the arrangements of the conductors.

TN-S

The TN-S is the first type of TN configuration. This configuration of system is typically used in industrial and commercial applications, where two different wires act as a protective conductor and a neutral conductor [1]. TN-S systems tend to be the safest option of the TN varieties due to the separation of the protective earthing and the neutral and can even be used with flexible conductors or smaller conduits.

Figure 1 TN S system diagram - Earthing System Types Explained
Figure 1: Diagram of a TN-S system

As can be seen in Figure 1 above, the TN-S system has the neutral and the protective earth (PE) connecting ground, from the same point, to the ECP using different conductors. TN-S systems can also be used in instances where there is no neutral (such as with a three-phase supply in a delta configuration), so long as there is a PE conductor present.

TN-C

The TN-C system is the second type of TN configuration. Unlike the TN-S configuration, the TN-C configuration combines the protective earthing and neutral into a single conductor. This is a configuration typical of utilities in North America, but not a recommended practice for industrial and commercial power systems [1]. One of the benefits of using a TN-C system is reduced cost, due to the elimination of a device pole and a conductor, but this compromise results in reduced safety (such as increased risk of fires or disruption by electromagnetic interference).

Figure 2 TN C system diagram - Earthing System Types Explained
Figure 2: Diagram of a TN-C system

As can be seen in Figure 2 above, the TN-C system differs from the TN-S system by combining the PE and neutral functions into a single conductor, the Protective Earth Neutral (PEN) conductor.

TN-C-S

The last type of TN system is the TN-C-S system. In North America, the transition point from PEN to PE is typical of the utility to user interface with inclusion of an electrode for an intentional connection to earth at the service entrance [1]. TN-C-S systems combine the benefits of the TN-C system with the TN-S system, but with reduced returns (i.e., TN-C-S systems are not as safe as TN-S system and not as cheap as TN-C systems).

Figure 3 TN C S system diagram - Earthing System Types Explained

Figure 3: Diagram of a TN-C-S system

As can be seen in Figure 3 above, the TN-C-S system combines the function of both the TN-C and TN-S systems, where certain ECPs will be connected to ground via the PEN conductor, and others will be connected to a PE and neutral conductor, both of which are split from the initial PEN conductor.

TT System

TT, or Terre-Terre, systems are electrical systems where the loads being supplied are connected to ground electrodes that are independent of ground electrodes connected to the source [1]. TT systems tend to not require continuous monitoring (with the exception of any RCDs, or residual current devices, connected to the ECPs). One deficit of the TT system is the high loop impedance, which causes high step voltages and leakage currents, meaning RCDs are required for the usage of this system.

Figure 4 TT system diagram - Earthing System Types Explained

Figure 4: Diagram of a TT system

From Figure 4 above, it can be seen that the system grounding occurs at two different points: The first being the point where the neutral conductor is connected, and the second being the point where the PE conductor is connected. These two grounding points are independent of each other.

IT System

IT, or isolation terre, systems are electrical systems where the source is insulated from the ground or connected to it with incredibly high impedance. To prevent potential damage from fault currents, IT systems are able to be earthed both individually and collectively [1]. IT systems offer the best continuity of service during operation (i.e., insulation faults are very easily caught and eliminated without much disruption), but also requires a high degree of maintenance. Additionally, the earth fault loop impedance is very high due to the high level of insulation in the network, and IT systems run the risk of having two simultaneous fault currents in the network.

Figure 5 IT individually earthed system diagram - Earthing System Types Explained

Figure 5: Diagram of an IT system with individually earthed ECPs

Figure 6 IT collectively earthed system diagram - Earthing System Types Explained

Figure 6: Diagram of an IT system with collectively earthed ECPs

Both Figure 5 and Figure 6 show examples of an IT system. Note that in both examples, the system is grounded through an incredibly high impedance (i.e., the open circuit), and the PE conductor is grounded separately. Figure 5 shows an instance where the ECPs have independent PE conductors, whereas Figure 6 shows an instance where the ECPs have a common PE conductor.

DC Systems

DC, or direct current, systems are a type of system earthing designed for direct current rather than AC, or alternating current. They are usually earthed via a positive and negative pole using a two-wire system [2]. The aforementioned systems have a DC system equivalent that differs from their AC counterparts functionally.

Comparison of Low Voltage Earthing Types

The advantages and disadvantages of the low voltage earthing methods are summarised below:

High voltage earthing systems

High voltage (above 1 kV) earthing systems have three fundamental requirements:

  1. Safety of people.

The earthing system shall not impose any person including those in the public population any unreasonable risk.

The main hazard to a person associated with earthing systems is current flowing through the heart leading to ventricular fibrillation.

  1. Protection of equipment.

The earthing system should provide for the expected operation without damage to any equipment. Specifically, this means the earthing system must be capable of (a) withstanding fault currents; (b) maintaining integrity for the lifetime of the installation; (c) avoiding damage to equipment due to excessive voltage rise or current flows during faults; and (d) contributing to ensure system electromagnetic compatibility.

  1. Operational security.

The earthing system must support operational security by maintaining a dependable voltage reference.

Solid grounding

Solid grounding refers to connecting a system supply, such as a generator neutral or a transformer, directly to the ground without any intervening impedances. This is a particularly good way to avoid excessive fault currents. The effectiveness of a solidly grounded system can be determined by comparing the ground-fault current to the three-phase fault current. The higher the ground-fault current compared to the three-phase fault current, the greater the degree of grounding in the system.

Ungrounded

In an ungrounded system, there is no direct connection whatsoever between the system supply and the ground. They are only connected to each other via capacitive coupling [1].

Figure 7 Ungrounded System circuit diagram and phasor diagram - Earthing System Types Explained

Figure 7: A circuit diagram and phasor diagram for an ungrounded system

Figure 7 shows a circuit diagram and a phasor diagram for an ungrounded system. Not that the system is grounded via 3 parallel capacitors, labelled XCO. These represent the capacitive coupling via which the system is grounded. Both the neutral and the protective earthing are grounded via this capacitance.

Resistance grounded

A resistance grounded system will have the system supply connected to the ground via a resistor. Limiting current via a resistor has several benefits, including reduction of burning and melting effects in faulted equipment, reduction of mechanical stresses in circuits, and reduction of electric-shock hazards to personnel, to name a few.

Figure 8 Resistance Grounded System - Earthing System Types Explained
Figure 8: Diagram of a three-phase system where the neutral is grounded via a resistor

Resistance grounded systems can be low-resistance or high-resistance, depending on the desired outcome. Low-resistance grounded systems can be beneficial for limiting the ground-fault current between 50 A and 1000A, whereas high-resistance grounded systems are good where the ground-fault current is less than 10 A in magnitude.

Reactance grounded

Resonant grounding and ground-fault neutralisers

Resonant grounding is the connection of a reactor between supply system neutral and ground to eliminate reactance in a system via resonance. Ground-fault neutralisers are the reactors that are connected between a system supply neutral and the ground. For the resonant grounding, the reactor is specially selected or tuned to resonate with the distributed capacitance of the system, so that the ground-fault current becomes mostly resistive with a low magnitude.

A reactance grounded system will have the system supply neutral connected to the ground via a reactor (capacitor, inductor, choke, etc). Reactance grounding is typically used when there is a desire to limit the ground fault magnitude to a value much like the magnitude of a three-phase fault.

Figure 9 Resonant grounded system - Earthing System Types Explained

Figure 9: Diagram of a resonance grounded system using ground-fault neutralisers

Figure 9 shows an example of a resonance grounded system, with the usage of a ground-fault neutraliser. Note that the introduction of the inductor, XL, is used to counter the effects of the capacitive coupling to the ground, thus making the ground fault current almost purely resistive.

Comparison of High Voltage Earthing System Types

The advantages and disadvantages of the high voltage earthing methods are summarised below:

Parameter Ungrounded Solid Reactance Grounding Ground-Fault Neutraliser Resistance Grounding
Low value reactor High value reactor Low Resistance High Resistance
Current for phase-to-ground fault in percent of three-phase current Less than 1% Varies, may be 100% or greater Usually designed to produce 25% to 100% 5% to 25% Nearly zero fault current 20% and downward to 100 A and 1000 A Less than 1% but not less than system charging element, 3ICO
Transient Very high Not excessive Not excessive Not excessive Not excessive Not excessive Not excessive
Line-to-neutral loads Not supported Supported Supported if current 60% or greater Not supported Not supported Not supported Not supported
Surge arresters Ungrounded-neutral type Ungrounded-neutral type
Remarks Not recommended due to overvoltages and nonsegregation of fault Generally used on systems (1) 600 V and below and (2) over 15 kV Not used due to excessive overvoltages Best suited for application in most medium voltage industrial and commercial systems that are isolated from their electric utility system by transformers Generally used on systems of 2.4 kV to 15 kV, particularly where large rotating machines are connected Used on systems up to 5 kV

Risk-based approach

Generally, it is incredibly difficult to eliminate all hazards associated with earthing systems. Risk management typically involves the minimisation of hazards to an acceptable statistical degree rather than eliminating them. Relatively new Standards such as AS 2067 [3] provide methodologies for risk-based calculations for earthing systems design.

Touch and step voltage hazards and the risk-based approach

The most significant threat facing a person involving earthing systems is the risk of ventricular fibrillation due to current flow in the heart. This depends on a person’s physiology, duration of current flow, amount of current and whether the current will interfere with the persons heart cycle. Details about the probabilities related to the effects of current on the human heart and heart/body impedance can be found in IEC 60479 [4].

Achieving negligible hazard levels is rarely possible. Determination of the hazard level is related to the risk of fibrillation and the usage of probability calculations as detailed in IEC 60479.

If hazards cannot be reduced, risk assessment must be employed. This should include the occurrence rate and duration of faults, along with the frequency and duration of contact for a person on-site. Risk mitigation should be applied as reasonably practicable, where the cost is not grossly disproportionate to the benefit gained.

References:

[1]  IEEE Std 3003.1-2019 Recommended Practice for System Grounding of Industrial and Commercial Power Systems.

[2]  IEC Std 60364-1 Low Voltage Electrical Installations – Part 1: Fundamental principles, assessment of general characteristics, definitions.

[3]  AS 2067:2016 Substations and high voltage installations exceeding 1 kV a.c.

[4]  IEC 60479-1:2018 Effects of current on human beings and livestock – Part 1: General aspects.

SafeGrid Earthing Software

Easily design safe earthing systems in compliance with Standards.

Related Articles:

Experienced electrical engineers created this reference list of standards for power systems earthing/grounding for substations, renewable energy, etc.
Understand how software simulations enhance grid impedance tests, improving accuracy and efficiency in earthing system design and performance evaluation.
This report explains how to perform accurate earth fault current analysis for substations connected by cable transmission lines. Earth fault currents for simple cable and overhead transmission lines are explained first. Next, two case studies involving hybrid cable transmission lines are presented.
Copper is often preferred for its superior electrical properties, while aluminum and galvanized steel are chosen for cost-effectiveness. Copper-clad steel can offer a balance between cost and performance. This article demonstrates which option is best for different scenarios.
The technical guide explains the electrical systems, local WTG and combined earthing system design, touch and step voltage hazards, soil electrical resistivity measurements, earth fault currents, earthing system software modelling, and validation testing of earthing for wind farms.
There are two reasons, according to the standards, why crushed rock or gravel is laid in substations, as explained in this article.

Print this article:

Print

SafeGrid Earthing Software

An electrical device with software and a graph on its screen.

Easily design safe earthing systems in compliance with Standards.

As used by:

SafeGrid Earthing Clients