Free Calculators

ELEK logo symbol only large size Kittl white - Voltage Drop Calculator
ELEKTM Power Engineering Software
ELEKTM Software

Voltage Drop Calculator

This calculator uses the accurate voltage drop equations from AS/NZS 3008.1. Accurate voltage drop calculations result in smaller cable sizes.

Read the FAQ section below for helpful tips.

Your Calculated Voltage Drop Is:

Why This Result?
The voltage drop has been calculated using the accurate equation that considers cable resistance and reactance, and load power factor.

The current ratings, cable resistance and cable reactance values used by this calculator were taken from AS/NZS 3008.1.1:2017 (based on IEC Standards).

Professional Electrical Design Software

A laptop, tablet, and smartphone display cable sizing software with various graphs, tables, and settings for cable installation and protection.

Cable Pro Software can do all the necessary electrical calculations and produce reports. Comprehensive Cloud-Based Software for Cable Sizing, Maximum Demand Calculations, Protection, Arc Flash Analysis, and LV Network Design

A laptop, tablet, and smartphone display cable sizing software with various graphs, tables, and settings for cable installation and protection.

Expert tips for voltage drop calculations

Frequently asked questions

How do I calculate voltage drop?

The balanced three-phase voltage drop equation is below. For single phase voltage drop replace the \(\sqrt{3}\) with 2 and \(V_{3ph}\) with \(V_{1ph}\).
Diagram of the accurate voltage drop equation for power cable calculations including resistance and power factor
Refer to our tutorial with a worked example of how to calculate voltage drop.
The current ratings, cable resistance and cable reactance values used by this calculator were taken from AS/NZS 3008.1.1:2017 (based on IEC Standards).
The effect of power factor on voltage drop explained:  For small cable sizes which have greater resistance than reactance a higher power factor results in a larger voltage drop. However for large cable sizes which have a high reactance compared with resistance the opposite is true.

Allowable voltage drop limits?

Refer to the article Voltage Drop Limits for LV Installations which lists all the voltage drop and voltage rise limits from the Standard AS/NZS 3000:2018.

How to convert power or horsepower into current?

The equations to convert the units of the electrical load inputs used by the calculator are as follows.

The load conversion from kW to A for single phase is calculated as:
\(I_{(A)}=\frac{1000\times P_{(kW)}}{PF\times V_{(V)}}\)
For three phase is calculated as:
\(I_{(A)}=\frac{1000\times P_{(kW)}}{\sqrt{3}\times PF\times V_{P-P(V)}}\)
Where PF is power factor and \(V_{P-P}\) is phase-to-phase voltage (i.e. 3-phase voltage).
The load conversion from kVA to A for single phase is calculated as:
\(I_{(A)}=\frac{1000\times S_{(kVA)}}{V_{(V)}}\)
For three phase is calculated as:
\(I_{(A)}=\frac{1000\times S_{(kVA)}}{\sqrt{3}\times V_{P-P(V)}}\)
The load conversion from horsepower (hp) to A for single phase is calculated as:
\(I_{(A)}=\frac{746\times hp}{V_{(V)}\times PF}\)
For three phase is calculated as:
\(I_{(A)}=\frac{746\times hp}{\sqrt{3}\times V_{P-P(V)}\times PF}\)

How do I calculate voltage rise instead of voltage drop?

How do I enter a 3-phase load current?

What should I enter for power factor?

How do I calculate the voltage drop for an unbalanced 3-phase system?

If the out-of-balance conditions are inconsistent or intermittent:

Where the currents in each phase are different in magnitudes for consistent periods:

Calculator inputs explained

Voltage (V)

Phase

Load

Power factor

Cable length (m)

Cores

Conductor

Insulation