Maximum Demand Tables

Maximum Demand Tables

Diversity factors for domestic and non-domestic installations
Motors in a factory setting_ELEK Software

After diversity maximum demand

Under normal operating conditions, not all the individual electrical equipment of an installation will operate at full load simultaneously. Therefore, the total circuit current is estimated using diversity factors and is often described as the ‘after diversity maximum demand’.

The diversity factors applicable to a given circuit in an installation depend on the type of installation (e.g., residential, commercial, industrial) and other factors.

You can calculate the Maximum Demand by hand or using software.

Cable Pro Web Software can perform Maximum Demand calculations by automatically applying the standards’ rules and balancing the loads to minimise the demand.

A double general power outlet (GPO) should be treated as two (2) points for the purpose of maximum demand calculations. For example, 19 double 10 A GPO’s equates to 38 points.

Tables for maximum demand calculation

Standards, such as the Wiring Rules AS/NZS 3000, provide diversity factors for typical installations and equipment loads.

The tables for domestic and non-domestic installations below are provided below. A table for calculating energy demand for non-domestic installations is also provided.

A common question is how to treat double socket outlets in maximum demand calculations. Double-socket outlets should be treated as two separate points.

Disclaimer:   No responsibility is assumed for the accuracy of the Tables below. Further, additional notes to these tables have not been included.

Table C1 Maximum Demand- Single and Multiple Domestic Electrical Installations

Load groupSingle domestic electrical installation or individual living unit per phase Blocks of living units
2 to 5 living units per phase6 to 20 living units per phase21 or more living units per phase
Loading associated with individual units
A. Lighting
(i) Except (ii) and load group H below
3 A for 1 to 20 points + 2 A for each additional 20 points or part thereof6 A5 A + 0.25 A per living unit0.5 A per living unit
(ii) Outdoor lighting exceeding a total of 1000 W75% connected loadNo assessment for the purpose of maximum demand
B.
(i) Socket-outlets not exceeding 10 A Permanently connected electrical equipment not exceeding 10 A and not included in other load groups
10 A for 1 to 20 points + 5 A for each additional 20 points or part thereof10 A + 5 A per living unit15 A + 3.75 A per living unit50 A + 1.9 A per living unit
(ii) Where the electrical installation includes one or more 15 A socket-outlets, other than socket-outlets provided to supply electrical equipment set out in groups C, D, E, F, G, and L 10 A
(iii) Where the electrical installation includes one or more 20 A socket-outlets other than socket-outlets provided to supply electrical equipment set out in groups C, D, E, F, G, and L 15 A
C. Ranges, cooking appliances, laundry equipment or socket-outlets rated at more than 10 A for the connection thereof 50% connection load15 A2.8 A per living unit
D. Fixed space heating or airconditioning equipment, saunas or socket-outlets rated at more than 10 A for the connection thereof 75% connected load75% connected load75% connected load
E. Instantaneous water heaters 33.3% connected load6 A per living unit100 A + 0.8 A per living unit
F. Storage water heaters Full-load current6 A per living unit100 A + 0.8 A per living unit
G. Spa and swimming pool heaters75% of the largest spa, plus 75% of the largest swimming pool, plus 25% of the remainder
H. Communal lighting Not applicableFull connected load
I. Socket-outlets not included in groups J and M below Permanently connected electrical equipment not exceeding 10 ANot applicable2 A per point, up to a maximum of 15 A
J. Appliances rated at more than 10 A and socket-outlets for the connection thereof-
(i) Clothesdryers, water heaters, self-heating washing machines, wash boilers
Not applicable50% connected load
(ii) Fixed space heating, airconditioning equipment, saunas Not applicable75% connected load
(iii) Spa and swimming pool heatersNot applicable 75% of the largest spa plus 75% of the largest swimming pool, plus 25% of the remainder
(vi) Charging equipment associated with electric vehicle100% connected load90% connected load75% connected load
K. LiftsIn accordance with Paragraph C2.4.1 and Table C2In accordance with Paragraph C2.4.1 and Table C2, for determination of size of submains
L. MotorsIn accordance with Paragraph C2.4.1 and Table C2, Column 2In accordance with Paragraph C2.4.1 and Table C2, Column 2
M. Appliances, including socket-outlets other than those set out in groups A to L above, e.g. pottery kilns, welding machines, radio transmitters, X-ray equipment and the likeConnected load 5 A or less: No assessment for purpose of maximum demandConnected load 10 A or less: No assessment for purpose of maximum deman
Connected load over 5 A: By assessmentConnected load over 10 A: By assessment

Table C2 Maximum Demand Non-Domestic Electrical Installations

Load groupResidential institutions, hotels, boarding houses, hospitals, accommodation houses, motelsFactories, shops, stores, offices, business premises, schools and churches
A. Lighting other than in load group F75% connected loadFull connected load
B.
(i) Socket-outlets not exceeding 10 A other than those in B (ii)
1000 W for first outlet plus 400 W for each additional outlet1000 W for first outlet plus 750 W for each additional outlet
(ii) Socket-outlets not exceeding 10 A in buildings or portions of buildings provided with permanently installed heating and cooling equipment or both1000 W for first socket-outlet, plus 100 W for each additional outlet
(iii) Socket-outlets exceeding 10 AFull current rating of highest rated socket-outlet, plus 50% of full current rating of remainderFull current rating of highest rated socket-outlet, plus 75% of full current rating of remainder
C.
(i) Appliances for cooking, heating and cooling, including instantaneous water heaters, but not appliances included in groups D and J below
Full connected load of highest rated socket-outlet, plus 50% of full current rating of remainderFull connected load of highest rated socket-outlet, plus 75% of full current rating of remainder
(ii) Charging equipment associated with electric vehiclesFull connected load of highest rated socket-outlet, plus 75% of full current rating of remainderFull connected load of highest rated socket-outlet, plus 75% of full current rating of remainder
D. Motors other than in E and F belowFull current rating of highest rated socket-outlet, plus 50% of full current rating of remainderFull load of highest rated motor, plus 75% of full load of second highest rated motor, plus 50% of full load of remainder
E. Lifts(i) Largest lift motor _ 125% full load
(ii) Next largest lift motor _ 75% full load
(iii) Remaining lift motors _ 50% full load
For the purpose of this load group, the full-load current of a lift motor shall mean the current taken from the supply when lifting maximum rated load at maximum rated speed
F. Fuel dispensing units(i) Motors : First motor _ full load
Second Motor _ 50% full load
Additional motors _ 25% full load
(ii)Lighting _ full connected load
G. Swimming pools, spas, saunas, thermal storage heaters including water heaters, space heaters, and similar arrangementsFull-load current
H. Welding machinesIn accordance with Paragraph C2.5.2, taking into account power factor correction
J. X-ray equipment50% of the full load of the largest x-ray unit, additional units being ignored
K. Other equipment not covered by load groups aboveBy assessment

Table C3 Maximum Demand – Energy Demand Method for non-Domestic Installations

Type of occupancyEnergy demand
Range, VA/m2Average, VA/m2
OfficesLight and Power
Air conditioning
-cooling
-reverse cycle
-zonal reheat
-variable volume
40-60

30-40
20-30
40-60
20
50

35
25
50
20
CarparksOpen Air
EV charging
Basement
EV charging
0-10
5-15
10-20
10-30
5
10
15
20
Retail ShopsLight and Power
Air conditioning
40-100
20-40
70
30
WarehousesLight and Power
Ventilation
Special Equipment
5-15
5
(use load details)
10
5

Light industrialLight and Power
Ventilation
Air conditioning
Special Equipment
10-20
10-20
30-50
(use load details)
15
15
40

Taverns, licensed clubsTotal60-10080
TheatresTotal80-120100
Cable Pro Web

Cable sizing and maximum demand software in the cloud. No installation, use on any device.

Related Articles:

Size active, neutral, and earth cables using AS/NZS 3008. The guide covers current capacity, voltage drop, and short-circuit calculations with examples.
Miniature Circuit Breakers (MCBs) protect against overcurrent in electrical circuits. MCBs are categorised based on their tripping characteristics, represented by different device curves such as Z, B, C, K, and D. This article offers guidance on selecting the right type for your application.
The AS/NZS 3000 Standard provides different rules in Appendix C for maximum demand with socket-outlets for domestic, commercial, and industrial electrical installations. Calculation examples are provided involving double socket-outlets.
The principle of economic cable sizing is to select a minimum cable size that is safe to use and the cost of the losses over the lifetime is also minimised.
Equations for calculating conduit sizes and space factors in accordance with standards are provided. Worked examples of conduit sizing calculations are provided.
The fault current which flows in a power cable causes its temperature to rise dramatically. The adiabatic equations for calculating the minimum conductor size to withstand the short circuit are explained.

Print this article: