Lightning Protection Module

SafeGrid Earthing Version 6.2

Table of Contents

Introduction

The Lightning Protection Module in SafeGrid Earthing Software allows the user to overlay lightning protection systems (LPS) such as lightning masts and earth wires over a PDF schematic. Using the Rolling Sphere Method (RSM), the Lightning Protection Module calculates the area protected by the masts and wires based on factors such as mast height, placement and the protection level used which determines the sphere radius. To access this module, open the SafeGridTM Earthing Software and select the Add-ons tab. Then, select the Lightning Protection Module.

Figure 1. – Add-ons module

Load a New Background

The number one in a yellow circle representing renewables.

Once the module has appeared, you can upload a PDF drawing by clicking on the Load new button. Figure 2 demonstrates this functionality using a 220 kV switchyard schematic as an example. You can download the PDF background drawing from the top of this webpage.

A yellow circle with the number two representing renewable power.

The Lightning Protection Module provides the option of selecting your desired Protection Level (PL) ranging from level 1 (20 m) to level 4 (60 m). A custom rolling sphere radius can also be entered under the User defined option in the Radius, R(m) dropdown box. It is common to consider that PL III using a sphere radius of 45 m provides ‘standard’ protection [1]. PL I and II with a sphere radius of 20 m and 30 m provides higher degrees of protection and therefore these protection levels will require a considerably greater number of air terminals.

Figure 2. – Loaded background with a PDF schematic

Set Height of Equipment

When considering your zones of protection, it is necessary to establish the maximum height of the equipment being protected by the LPS. In Figure 3, the substation layout drawing below the maximum equipment height for the protected zone has been established within the red boxes. Figure 4 provides a side view dimension that displays the height of lightning masts.

Figure 3. – Overall heights of equipment to be protected

Figure 4. – Critical height of equipment to be protected

From Figure 5 , the heights of the equipment can be input into the top right-hand corner.

The yellow circle represents the number 3 in an electrical world.

You can select the number of equipment heights by clicking on the up and down arrow keys.

A yellow circle representing a digital electrical substation with the number 4.

 Each equipment height is input in metres. For the 220 kV substation example, an equipment height of 10.5 m is given.

Figure 5. – Inputting equipment heights

Define Masts and Set Positions

In Figure 6, the purple boxes represent the positions for the lightning protection systems, i.e. lightning posts (LP). Select the protection level you wish to use to cover your structure; in the case of the substation, a protection level of 2 is selected. Then, click the Add Mast button as per Figure 7. This will bring up a small window where you can define the air terminal height.

Figure 6. – Lightning masts at various positions

Each mast can be selected by clicking with the left mouse button and the masts can be moved into position using the mouse. For the substation example, the wires and masts used are listed in Table 1.

Figure 7. – Adding a mast

Table 1. – Mast and wire data

ID Overall Height (m) Air Terminal Height (m) Structure Height (m) Description
1 21.5 1.5 20 Lightning mast
2 21.5 1.5 20 Lightning mast
3 17.5 1.5 16 Lightning post (Building mounted)
4 17.5 1.5 16 Lightning post (Building mounted)
5 21.5 1.5 20 Lightning mast
6 21.5 1.5 20 Lightning mast
7 21.5 1.5 20 Lightning mast
8 20 0 20 Lightning post (Gantry)
9 20 0 20 Lightning post (Gantry)
10 20 0 20 Earthing wire
11 20 0 20 Earthing wire

Calculating Protected Area

Once all masts have been positioned and defined, the Calculate button will compute the area protected by the masts based on the RSM. This is showcased in Figure 8 with the blue area indicating the area protected against lightning strikes. To extend the area of protection, earth wires can be added by selecting the Add Wire button where you can choose the wire’s origin and destination based on the lightning mast numbers. When pressing the Edit Wire button, you can also define the percentage of sag for the wire. To save the overlay results, click the Save button. This will save the results as an XML file.

Figure 8. – Calculated result

Report and Mast List

After calculating the area of protection, you can generate a report by clicking the Report button in the top left-hand corner. This will produce an image of the schematic including your overlay and equipment height. The second page will produce the lightning mast data displaying the heights and positions. Wire data will also be displayed showing the origin and destination of the wire including sag percentage.

References

[1] AS/NZS 1768, Lightning Protection.

[2] IEC 62305, Protection Against Lightning.

Related Tutorials:

This tutorial shows how to use the Fault Current Distribution module in ELEK SafeGrid Earthing Software to model an earth fault on an overhead transmission line with an underground cable link.
With the Fall of Potential Test, the resistance of an earthing system is measured using a remote earth electrode. There is a theoretical position of 61.8 % of the separation distance between the measured grid and the remote electrode, which is the correct position for measuring the exact grid impedance for uniform soil resistivity but not for multilayer soils. This tutorial shows ELEK SafeGrid Earthing Software users how to simulate an FOP test.
This video tutorial focuses on the design and modelling of Earthing Systems for Wind Farms and Solar PV Farms. Real-world examples are provided and are explained.
ELEK SafeGrid Earthing Software can perform calculations in the time domain such as for lightning currents. Transient waveforms are composed of many frequency components and Fourier transforms are used. The transient waveform types include IEC 62305, CIGRE, Heidler, Double-exponential, and Custom. The time-domain response of an earthing system can be analysed.
SafeGrid can model custom earthing arrangements of any size or shape in 2D or 3D. You can specify the grid using the in-built editor tools or you can import grids drawn in AutoCAD.
This video (25 min) tutorial shows the main features of SafeGrid Earthing Software for performing an earthing designs and explains the design process.