표면 재질 저항률

Typical resistivity values of surface layer materials used in substations
Crushed blue metal rock and foundation in switchyard 1 scaled - Surface Material Resistivity

Why use surface material layers in substations?

Inside a substation (often as well as outside the perimeter fence) you will notice a layer of rock or crushed stone, or asphalt. The thickness of this additional surface layer typically ranges from 8-15 cm and there are two main reasons for including it being that:

  1. It helps to avoid the drying out of topsoil layers during prolonged dry weather periods; and
  2. It has a very large effect on reducing body currents resulting from touch and step voltages involving a person’s feet.

With regards to the second point, field tests with and without the surface layer have revealed a reduction in body currents in the order of 20 time less. Therefore, covering the surface with a material of high resistivity is very valuable in reducing electric shock currents so it’s common practice. Note it is very important that the integrity of the surface layers is maintained to avoid a compromise in safety.

How to use surface layers for earthing designs

The additional surface layer is included in our calculations for safe touch and step voltage limits using software. When no specific information about the actual surface material resistivity is available the following data may be used [3]:

  • Typical crushed rock has a wet resistivity of 3000 Ω.m and a min. thickness of 100 mm.
  • Typical asphalt has a wet resistivity of 10,000 Ω.m and a min. thickness of 50 mm. Mitigation of touch or step voltages using asphalt layer should not be performed where touch or step voltages exceed 3 kV and 5 kV respectively due to low flashover withstand of asphalt.

It is up to the designer to confirm wet resistivity value of the actual material being used at site is at least as high as those being assumed in the design model.

Typical surface material resistivities

Typical wet and dry resistivities of materials used for substations are given in Table 1 [1]. Local conditions, size, and type of stone may affect the value of resistivity therefore it is important that the resistivity of rock samples typical of the type being used in a given area be measured.

Table 1—Typical surface material resistivities

Number Description of surface material (U.S. state where found) Resistivity of sample ohm-meter
Dry 습식
1 Crusher run granite with fines (NC) 140 × 10 6 1300 (ground water, 45 Ω.m)
2 1.5 in (0.04 m) crusher run granite (GA) with fines 4000 1200 (rain water, 100 Ω.m)
3 0.75 in to 1 in (0.02 m to 0.025 m) granite (CA) with fines -- 6513 (10 min after 45 Ω.m water drained)
4 #4 (1 in to 2 in) (0.025 m to 0.05 m) washed granite (GA) 1.5 × 106 to 4.5 × 106 5000 (rain water, 100 Ω.m
5 #3 (2 in to 4 in) (0.05 m to 0.1 m) washed granite (GA) 2.6 × 106 to 3 × 106 10 000 (rain water, 100 Ω.m)
6 Size unknown, washed limestone (MI) 7 × 106 2000 to 3000 (ground water, Ω.m)
7 Washed granite, similar to 0.75 in (0.02 m) gravel 2 × 106 10 000
8 Washed granite, similar to pea gravel 40 × 106 5000
9 #57 (0.75 in) (0.02 m) washed granite (NC) 190 × 106 8000 (ground water, 45 Ω.m)
10 Asphalt 2 × 106 to 30 × 106 10 000 to 6 × 106
11 Concrete 1 × 106 to 1 × 109a 21 to 100

Note that over time the resistivity of surface materials may be reduced through compression and other environmental factors resulting in filling of voids. A surface material exposed to sea spray may have substantially lower resistivity than for that same material installed at inland substations. These factors should be considered during the design phase as well as after the substation is in service.

It is usually recommended that wet resistivity tests be performed for a particular surface layer stone being used for a substation project or by a power utility. The resistivity test of a crushed rock sample is relatively simple (refer to [2]) and does not require a complex laboratory setup.

참조:

[1] IEEE Std 80 - AC 변전소 접지 안전에 대한 IEEE 가이드

[2] IEEE Std 81:2012 – IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Grounding System

[3] ENA EG-0:2010 – Power system earthing guide.

SafeGrid 접지 소프트웨어

표준에 따라 안전한 접지 시스템을 쉽게 설계할 수 있습니다.

관련 문서:

숙련된 전기 엔지니어들이 변전소, 재생 에너지 등을 위한 전력 시스템 접지/접지에 대한 이 표준 참조 목록을 만들었습니다.
소프트웨어 시뮬레이션이 어떻게 그리드 임피던스 테스트를 향상시켜 접지 시스템 설계 및 성능 평가의 정확성과 효율성을 개선하는지 알아보세요.
이 보고서에서는 케이블 송전선으로 연결된 변전소에 대한 정확한 지락 전류 해석 방법을 설명합니다. 먼저 단순 케이블 및 가공 송전선로의 지락 전류에 대해 설명합니다. 다음으로 하이브리드 케이블 송전선로와 관련된 두 가지 사례 연구를 제시합니다.
구리는 우수한 전기적 특성 때문에 선호되는 반면, 알루미늄과 아연 도금 강철은 비용 효율성을 위해 선택되는 경우가 많습니다. 구리 피복 강철은 비용과 성능 사이의 균형을 제공할 수 있습니다. 이 문서에서는 다양한 시나리오에 어떤 옵션이 가장 적합한지 설명합니다.
이 기술 가이드에서는 전기 시스템, 로컬 WTG 및 복합 접지 시스템 설계, 터치 및 계단 전압 위험, 토양 전기 저항 측정, 접지 오류 전류, 접지 시스템 소프트웨어 모델링, 풍력 발전소 접지 검증 테스트에 대해 설명합니다.
이 문서에 설명된 대로 쇄석이나 자갈을 변전소에 깔아두는 이유는 두 가지입니다.