Surface Material Resistivity

Typical resistivity values of surface layer materials used in substations
Crushed blue metal rock and foundation in switchyard 1 scaled - Surface Material Resistivity

Why use surface material layers in substations?

Inside a substation (often as well as outside the perimeter fence) you will notice a layer of rock or crushed stone, or asphalt. The thickness of this additional surface layer typically ranges from 8-15 cm and there are two main reasons for including it being that:

  1. It helps to avoid the drying out of topsoil layers during prolonged dry weather periods; and
  2. It has a very large effect on reducing body currents resulting from touch and step voltages involving a person’s feet.

With regards to the second point, field tests with and without the surface layer have revealed a reduction in body currents in the order of 20 time less. Therefore, covering the surface with a material of high resistivity is very valuable in reducing electric shock currents so it’s common practice. Note it is very important that the integrity of the surface layers is maintained to avoid a compromise in safety.

How to use surface layers for earthing designs

The additional surface layer is included in our calculations for safe touch and step voltage limits using software. When no specific information about the actual surface material resistivity is available the following data may be used [3]:

  • Typical crushed rock has a wet resistivity of 3000 Ω.m and a min. thickness of 100 mm.
  • Typical asphalt has a wet resistivity of 10,000 Ω.m and a min. thickness of 50 mm. Mitigation of touch or step voltages using asphalt layer should not be performed where touch or step voltages exceed 3 kV and 5 kV respectively due to low flashover withstand of asphalt.

It is up to the designer to confirm wet resistivity value of the actual material being used at site is at least as high as those being assumed in the design model.

Typical surface material resistivities

Typical wet and dry resistivities of materials used for substations are given in Table 1 [1]. Local conditions, size, and type of stone may affect the value of resistivity therefore it is important that the resistivity of rock samples typical of the type being used in a given area be measured.

Table 1—Typical surface material resistivities

Number Description of surface material (U.S. state where found) Resistivity of sample ohm-meter
Seco Mojado
1 Crusher run granite with fines (NC) 140 × 10 6 1300 (ground water, 45 Ω.m)
2 1.5 in (0.04 m) crusher run granite (GA) with fines 4000 1200 (rain water, 100 Ω.m)
3 0.75 in to 1 in (0.02 m to 0.025 m) granite (CA) with fines -- 6513 (10 min after 45 Ω.m water drained)
4 #4 (1 in to 2 in) (0.025 m to 0.05 m) washed granite (GA) 1.5 × 106 to 4.5 × 106 5000 (rain water, 100 Ω.m
5 #3 (2 in to 4 in) (0.05 m to 0.1 m) washed granite (GA) 2.6 × 106 to 3 × 106 10 000 (rain water, 100 Ω.m)
6 Size unknown, washed limestone (MI) 7 × 106 2000 to 3000 (ground water, Ω.m)
7 Washed granite, similar to 0.75 in (0.02 m) gravel 2 × 106 10 000
8 Washed granite, similar to pea gravel 40 × 106 5000
9 #57 (0.75 in) (0.02 m) washed granite (NC) 190 × 106 8000 (ground water, 45 Ω.m)
10 Asphalt 2 × 106 to 30 × 106 10 000 to 6 × 106
11 Concrete 1 × 106 to 1 × 109a 21 to 100

Note that over time the resistivity of surface materials may be reduced through compression and other environmental factors resulting in filling of voids. A surface material exposed to sea spray may have substantially lower resistivity than for that same material installed at inland substations. These factors should be considered during the design phase as well as after the substation is in service.

It is usually recommended that wet resistivity tests be performed for a particular surface layer stone being used for a substation project or by a power utility. The resistivity test of a crushed rock sample is relatively simple (refer to [2]) and does not require a complex laboratory setup.

Referencias:

[1] IEEE Std 80 - Guía IEEE para la seguridad en la puesta a tierra de subestaciones de CA

[2] IEEE Std 81:2012 – IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Grounding System

[3] ENA EG-0:2010 – Power system earthing guide.

Software de puesta a tierra SafeGrid

Diseñe fácilmente sistemas de puesta a tierra seguros de conformidad con las normas.

Artículos relacionados:

Ingenieros eléctricos experimentados crearon esta lista de referencia de normas para la puesta a tierra de sistemas de energía para subestaciones, energías renovables, etc.
Entender cómo las simulaciones de software mejoran las pruebas de impedancia de red, mejorando la precisión y la eficiencia en el diseño de sistemas de puesta a tierra y la evaluación del rendimiento.
Este informe explica cómo realizar un análisis preciso de la corriente de defecto a tierra para subestaciones conectadas por líneas de transmisión por cable. En primer lugar, se explican las corrientes de defecto a tierra para líneas de transmisión por cable simples y aéreas. A continuación, se presentan dos casos prácticos de líneas de transmisión por cable híbridas.
A menudo se prefiere el cobre por sus propiedades eléctricas superiores, mientras que el aluminio y el acero galvanizado se eligen por su rentabilidad. El acero revestido de cobre puede ofrecer un equilibrio entre coste y prestaciones. En este artículo se muestra cuál es la mejor opción en cada caso.
La guía técnica explica los sistemas eléctricos, el diseño de los WTG locales y del sistema combinado de puesta a tierra, los riesgos de tensión de contacto y de paso, las mediciones de la resistividad eléctrica del suelo, las corrientes de defecto a tierra, el modelado del software del sistema de puesta a tierra y las pruebas de validación de la puesta a tierra para parques eólicos.
Hay dos razones, según las normas, por las que se coloca roca triturada o grava en las subestaciones, como se explica en este artículo.

Imprima este artículo:

Imprimir

Software de puesta a tierra SafeGrid

Un aparato eléctrico con software y un gráfico en su pantalla.

Diseñe fácilmente sistemas de puesta a tierra seguros de conformidad con las normas.

Utilizado por:

Clientes de puesta a tierra SafeGrid