Résistivité du matériau de surface

Typical resistivity values of surface layer materials used in substations
Crushed blue metal rock and foundation in switchyard 1 scaled - Surface Material Resistivity

Why use surface material layers in substations?

Inside a substation (often as well as outside the perimeter fence) you will notice a layer of rock or crushed stone, or asphalt. The thickness of this additional surface layer typically ranges from 8-15 cm and there are two main reasons for including it being that:

  1. It helps to avoid the drying out of topsoil layers during prolonged dry weather periods; and
  2. It has a very large effect on reducing body currents resulting from touch and step voltages involving a person’s feet.

With regards to the second point, field tests with and without the surface layer have revealed a reduction in body currents in the order of 20 time less. Therefore, covering the surface with a material of high resistivity is very valuable in reducing electric shock currents so it’s common practice. Note it is very important that the integrity of the surface layers is maintained to avoid a compromise in safety.

How to use surface layers for earthing designs

The additional surface layer is included in our calculations for safe touch and step voltage limits using software. When no specific information about the actual surface material resistivity is available the following data may be used [3]:

  • Typical crushed rock has a wet resistivity of 3000 Ω.m and a min. thickness of 100 mm.
  • Typical asphalt has a wet resistivity of 10,000 Ω.m and a min. thickness of 50 mm. Mitigation of touch or step voltages using asphalt layer should not be performed where touch or step voltages exceed 3 kV and 5 kV respectively due to low flashover withstand of asphalt.

It is up to the designer to confirm wet resistivity value of the actual material being used at site is at least as high as those being assumed in the design model.

Typical surface material resistivities

Typical wet and dry resistivities of materials used for substations are given in Table 1 [1]. Local conditions, size, and type of stone may affect the value of resistivity therefore it is important that the resistivity of rock samples typical of the type being used in a given area be measured.

Table 1—Typical surface material resistivities

Number Description of surface material (U.S. state where found) Resistivity of sample ohm-meter
Secs Humide
1 Crusher run granite with fines (NC) 140 × 10 6 1300 (ground water, 45 Ω.m)
2 1.5 in (0.04 m) crusher run granite (GA) with fines 4000 1200 (rain water, 100 Ω.m)
3 0.75 in to 1 in (0.02 m to 0.025 m) granite (CA) with fines -- 6513 (10 min after 45 Ω.m water drained)
4 #4 (1 in to 2 in) (0.025 m to 0.05 m) washed granite (GA) 1.5 × 106 to 4.5 × 106 5000 (rain water, 100 Ω.m
5 #3 (2 in to 4 in) (0.05 m to 0.1 m) washed granite (GA) 2.6 × 106 to 3 × 106 10 000 (rain water, 100 Ω.m)
6 Size unknown, washed limestone (MI) 7 × 106 2000 to 3000 (ground water, Ω.m)
7 Washed granite, similar to 0.75 in (0.02 m) gravel 2 × 106 10 000
8 Washed granite, similar to pea gravel 40 × 106 5000
9 #57 (0.75 in) (0.02 m) washed granite (NC) 190 × 106 8000 (ground water, 45 Ω.m)
10 Asphalt 2 × 106 to 30 × 106 10 000 to 6 × 106
11 Concrete 1 × 106 to 1 × 109a 21 to 100

Note that over time the resistivity of surface materials may be reduced through compression and other environmental factors resulting in filling of voids. A surface material exposed to sea spray may have substantially lower resistivity than for that same material installed at inland substations. These factors should be considered during the design phase as well as after the substation is in service.

It is usually recommended that wet resistivity tests be performed for a particular surface layer stone being used for a substation project or by a power utility. The resistivity test of a crushed rock sample is relatively simple (refer to [2]) and does not require a complex laboratory setup.

Références :

[1] IEEE Std 80 – IEEE Suide for Safety in AC Substation Grounding

[2] IEEE Std 81:2012 – IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Grounding System

[3] ENA EG-0:2010 – Power system earthing guide.

Logiciel de mise à la terre SafeGrid

Concevoir facilement des systèmes de mise à la terre sûrs, conformes aux normes.

Articles connexes :

Des ingénieurs électriciens expérimentés ont créé cette liste de référence de normes pour la mise à la terre des systèmes électriques pour les sous-stations, les énergies renouvelables, etc.
Comprendre comment les simulations logicielles améliorent les tests d'impédance du réseau, en améliorant la précision et l'efficacité de la conception et de l'évaluation des performances des systèmes de mise à la terre.
Ce rapport explique comment effectuer une analyse précise du courant de défaut à la terre pour les sous-stations connectées par des lignes de transmission par câble. Les courants de défaut à la terre pour les câbles simples et les lignes de transmission aériennes sont d'abord expliqués. Ensuite, deux études de cas impliquant des lignes de transmission par câble hybride sont présentées.
Le cuivre est souvent préféré pour ses propriétés électriques supérieures, tandis que l'aluminium et l'acier galvanisé sont choisis pour leur rentabilité. L'acier revêtu de cuivre peut offrir un équilibre entre le coût et la performance. Cet article montre quelle est la meilleure option en fonction des différents cas de figure.
Le guide technique explique les systèmes électriques, la conception des groupes électrogènes locaux et des systèmes de mise à la terre combinés, les risques de tension de contact et d'échelon, les mesures de résistivité électrique du sol, les courants de défaut à la terre, la modélisation logicielle des systèmes de mise à la terre et les tests de validation de la mise à la terre pour les parcs éoliens.
Selon les normes, la pose de pierres concassées ou de gravier dans les sous-stations se justifie pour deux raisons, comme l'explique cet article.