접지봉 및 로드 베드의 저항

Equations for calculating earthing rod resistance validated with software
A man is digging a hole in the ground with a shovel.

How earthing rods improve safety

Earthing rods are bare metal stakes driven vertically into the ground installed as standalone or in groups as part of an earthing system. Earthing rods may improve safety by reducing earthing grid resistance and reducing touch voltages when driven into low resistivity soil layers.

 Our article on the Fundamentals of Earthing Design explains more.

How far apart to separate earthing rods

For larger earthing systems multiple rods may be connected in the form of rod beds. The individual rods of rod beds should not be installed too close to one another due to the proximity effect which reduces their efficiency. Figure 1 shows how the fields of rods affects other rods while they are dissipating current into the ground during a fault.

The general rule of thumb is earth rods should be separated by at least their driven length.

전력선을 표시하는 다이어그램입니다.
Figure 1 - Proximity effect between two adjacent earth rods

Should earthing rods be encased in concrete?

IEEE Std. 80 [ref. 1] states that encasing rods in concrete may be effective at improving the performance of buried rods. Our article on Concrete-encased Earthing Rods explains more.

Calculating earthing rod resistance

Equations for calculating resistance of individual rods, groups of bare rods and rods encased in concrete are given below. There is also a free Earth Rods Resistance Calculator. Example calculations are given below and the results are validated with SafeGrid Earthing Software.

Single earthing rod equation

단일 막대 저항[1]을 계산하는 데 사용되는 일반적인 공식은 다음과 같습니다:

11 - Resistance of Earthing Rods and Rod Beds

Where:

ρ:the resistivity of the soil (Ω.m)
Lr:length of the rod
d: diameter of the ground rod.

Rods bed equation

The simple equation used to calculate the rods bed resistance is given by Schwarz [ref. 1] as:

A diagram of a chemical equation formula.

Where:

ρ: Soil resistivity (Ω.m)
nr: Number of rods
Lr: Length of rod (m)
d: diameter of the rod (mm)
A: Grid area (m2)
K1: coefficients

The coefficient K1 formula was given by Kercel [ref. 2] as:

An example of a mathematical formula related to power and renewables.

Where a is the length of the grid and b is the width of the grid.

Rods bed encased in concrete equation

To reduce the soil resistivity around the rod (thus making it more effective) a low resistivity layer is added around it to increase its effectiveness while lowering the cost of materials. With the inclusion of concrete in equation (1), we get the following equation:
eq4 - Resistance of Earthing Rods and Rod Beds
Equation 4 - Resistance of Earthing Rods and Rod Beds

Where:
ρc: the resistivity of concrete (Ω.m)
Dc: Diameter of the concrete shell (mm)

Example hand calculations and software validation

Example 1 – Rods bed resistance

In this example we calculated the resistance of a 20 m by 10 m meshed grid shown Figure 2 which had 15 rods which are 5 m long buried at 0.5 m and were each separated by 5 m. The soil model is 100 Ω.m uniform.

Note that Equation 2 does not consider the effects of the horizontal connected conductors, which is a drawback of the simple equation approach. Therefore, in the SafeGrid software model the horizontal conductors connecting the tops of the rods together were insulated.

For the rod bed in Figure 2, Equation 2 gives a resistance of 3.19 Ω. SafeGrid software calculates 2.851 Ω for the same rod bed arrangement which is 10.6 % lower.

A diagram of a row of power squares.
Figure 2. Software model of rods bed with insulated horizontal conductors
Figure 3. Software results for rod bed
Figure 3. Software results for rod bed

To examine the proximity effects, we varied the spacing between the 5 m rods from 1m (separation factor = 0.2) up to 10 m (separation factor = 2) and calculated resistance.

Figure 4 shows that the simple rod bed resistance equation captures the proximity effect as confirmed by the SafeGrid software model results. The optimal separation between rods is when the separation distance is equal to the rod length.

Figure 4. Rod bed resistances of bare rods
Figure 4. Rod bed resistances of bare rods

Example 2 – Concrete-encased rod bed resistance

In this example the grid is the same as in Example 1 except the rods are encased in concrete with a shell diameter of 200 mm. and the concrete has resistivity of 30 Ω.m which is lower than the native soil resistivity of 100 Ω.m uniform.

For the rod bed in Figure 5, Equation 4 gives a resistance of 2.96 Ω which is lower than the result in Example 1 without concrete encasing of rods.

SafeGrid software calculates the resistance for the concrete-encased rod bed to be 2.545 Ω.

Figure 5. Software model of concrete-encased rods bed with insulated horizontal conductors
Figure 5. Software model of concrete-encased rods bed with insulated horizontal conductors
A graph illustrating the diverse array of colors representing different electrical power sources, including renewables.
Figure 6. Software results for concrete-encased rod bed

To examine the proximity effects, we varied the spacing between the 5 m rods from 1m (separation factor = 0.2) up to 10 m (separation factor = 2) and calculated resistance.

Figure 7 shows how rod bed resistance varies for concrete-encased grid using the simple equation and using SafeGrid software. Once again, the plot confirms that optimal separation between rods is when the separation distance is equal to the rod length.

Figure 7. Rod bed resistances of concrete-encased rods
Figure 7. Rod bed resistances of concrete-encased rods

권장 사항

The simple equations from IEEE Std. 80 [ref. 1] for rod resistance and rod bend resistance have been extended to include the effects of concrete-encasing of the rods. The simple equations appear to capture the proximity effect for rods reasonably. 

The significant limitations of using the simple equations includes:

  • They can only model simple rod arrays with equal separations.
  • They cannot model the horizontal interconnecting conductors.
  • They are limited to only uniform soil models.

Most soils have a multilayer soil resistivity structure. Importantly, rods should in general be used when the bottom layer resistivity is lower than the top layers and the rods should be sufficiently long to penetrate the low resistivity layers.

The significant advantages to using software to model earthing systems includes:

  • Software can model arbitrary earthing arrangements for multi-layered soils resistivity structures.
  • Software results are more accurate resulting in higher degrees of safety and cost savings due to more economical earthing system installations.

참조:

[1] ‘IEEE Guide for Safety in AC Substation Grounding.’ IEEE Std. 80-2013.
[2] Kercel, S. W., “Design of switchyard grounding systems using multiple grids” IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no. 3, pp. 1341–1350, Mar. 1981.

SafeGrid 접지 소프트웨어

표준에 따라 안전한 접지 시스템을 쉽게 설계할 수 있습니다.

관련 문서:

숙련된 전기 엔지니어들이 변전소, 재생 에너지 등을 위한 전력 시스템 접지/접지에 대한 이 표준 참조 목록을 만들었습니다.
소프트웨어 시뮬레이션이 어떻게 그리드 임피던스 테스트를 향상시켜 접지 시스템 설계 및 성능 평가의 정확성과 효율성을 개선하는지 알아보세요.
이 보고서에서는 케이블 송전선으로 연결된 변전소에 대한 정확한 지락 전류 해석 방법을 설명합니다. 먼저 단순 케이블 및 가공 송전선로의 지락 전류에 대해 설명합니다. 다음으로 하이브리드 케이블 송전선로와 관련된 두 가지 사례 연구를 제시합니다.
구리는 우수한 전기적 특성 때문에 선호되는 반면, 알루미늄과 아연 도금 강철은 비용 효율성을 위해 선택되는 경우가 많습니다. 구리 피복 강철은 비용과 성능 사이의 균형을 제공할 수 있습니다. 이 문서에서는 다양한 시나리오에 어떤 옵션이 가장 적합한지 설명합니다.
이 기술 가이드에서는 전기 시스템, 로컬 WTG 및 복합 접지 시스템 설계, 터치 및 계단 전압 위험, 토양 전기 저항 측정, 접지 오류 전류, 접지 시스템 소프트웨어 모델링, 풍력 발전소 접지 검증 테스트에 대해 설명합니다.
이 문서에 설명된 대로 쇄석이나 자갈을 변전소에 깔아두는 이유는 두 가지입니다.

이 문서를 인쇄하세요:

인쇄

SafeGrid 접지 소프트웨어

화면에 소프트웨어와 그래프가 표시되는 전기 장치입니다.

표준에 따라 안전한 접지 시스템을 쉽게 설계할 수 있습니다.

사용처

SafeGrid 접지 클라이언트