예제와 함께 전압 강하 계산 방법

예제와 함께 전압 강하 계산 방법

Accurate voltage drop, balanced or unbalanced with calculations explained

What is voltage drop?

The voltage drop in a circuit represents the difference between the voltage from the supply end and the voltage at the load end. Voltage drop depends on the current load, cable type, and other factors, and has a significant impact on the minimum cable size.

The standards set allowable percentage voltage drop limits.

Voltage drop equation

When determining the maximum voltage drop, an equation can be applied under the assumption that the power factor of the cable is equal to that of the load.

This equation can be expressed as:

\(V_d = I \cdot Z_c\)     (Eq. 1)

Where:

    • Vd is voltage drop in cable, in volts
    • I is current flowing through cable in amperes
    • Zc is impedance of conductors in ohms whereby,= √((Rc2+ Xc2))

Rc represents cable resistance which is a function of conductor material, size and operating temperature. Xc represents cable reactance being a function of shape and phase spacing.

Note for DC voltage drop calculations the value for reactance Xis zero.

Use the Free Voltage Drop Calculator for easy and accurate voltage drop calculations.

Voltage drop based on power factor

In a case where the supply and load voltages differ in terms of phase angle, another set of equations are to be used to compensate for this change. When the current is leading the voltage, the supply voltage ends up being smaller than the load voltage. The voltage drop IZc is identical in all power factor cases but is different in terms of phase angle except for when the cable and load power factors are equal which shows the voltage drop Vd is a maximum of IZc. The following equations apply for lagging power factors.

For a single-phase system

\(V_{d1\phi} = IL[2(R_c cos \theta + X_c sin \theta)]\)    (Eq. 2)

For a balanced three-phase system

\(V_{d3\phi} = IL[\sqrt{3}(R_c cos \theta + X_c sin \theta)]\)    (Eq. 3)

Resistance and cable operating temperature

The resistance of a cable is dependent on temperature and the standard provides tables of resistance for a particular operating temperature.

In a situation where the cable operating temperature is less than the maximum figure provided by the Standard tables, the conductor temperature can be estimated using the following equation:

 

\(\theta_{0} = (\theta_{R} – \theta_{A})(\frac{I_0}{I_R})^2 + \theta_{A}\)    (Eq. 4)

 

Where: 

  • I0 = operating current, in amperes
  • IR = rated current provided in the current rating tables (from Tables 4-21 in AS/NZS 3008.1)
  • 00= operating temperature of cable when carrying , in degrees Celsius
  • 0A= ambient air or soil temperature, in degrees Celsius.

Once cable operating temperature is calculated then the cable resistance can be selected. In the case of AS/NZS 3008.1 the Tables 34-50 provides resistance values for the following operating temperatures 45oC, 60oC, 75oC, 80oC, 90oC, 110oC and the calculated operating temperature is then raised (more conservative) to the nearest temperature.

Voltage drop for unbalanced multiphase circuits

In an unbalanced system, current will be flowing through the neutral conductor as illustrated by the phasor diagram in Figure 1:

processed 6633f313 eb09 4bcd af31 9b3b31664d6b m4i0GfUZ - Voltage Drop Calculation Method with Examples
Figure 1: Phasor diagram for an unbalanced system

There are two ways of dealing with voltage drop in these cases. A conservative solution is to assume a balanced three-phase load and to perform calculations using the current flowing in the heaviest loaded phase. However, where the currents in each phase can be shown to be of different magnitudes for consistent periods then voltage drop can be calculated on a single-phase basis by summing the voltage drop in the heaviest loaded phase plus the voltage drop in the neutral as shown by the equation below.

 

 

\(V_d = I_A L_A Z_{cA} + I_N L_N Z_{cN}\)    (Eq. 5)

 

In the next section, we will provide an example voltage drop calculation.

Example voltage drop calculation

Single core cables with copper conductors and XLPE insulated are connected to a 3 phase 400 V supply. The installation is buried direct in the ground (reference ambient temperature is 25oC) over 120 m length of run. The load current is 240 A at power factor of 0.9.

What is the 3-phase voltage drop?

 

Step 1: Determine cable operating temperature

The minimum conductor size from current-rating Table 8, column 22 is 70 mm2 which has a maximum current rating of 277 A.
processed 0fd22572 7716 4175 bde3 678c06e60a7d 1gxuILjI - Voltage Drop Calculation Method with Examples

Figure 2: Illustration of the cable buried directly in the ground.

The normal use operating temperature for XLPE insulated cables is 90˚C. Using Equation 4 for cable operating temperature:

\(\theta_0 = (90^{\circ} – 25^{\circ})(\frac{240}{277})^2 + 25^{\circ}\)

Step 2: Determine cable resistance based on cable operating temperature

Using Table 34 (refer to Appendix 1 below) we can find the AC resistance of the cable matching with the conductor size and at the conductor temperature nearest to the cable operating temperature calculated in Step 1. Since we calculated a temperature of 73.8°, we should round up the temperature and assume that 75° is the most accurate temperature to use.

Per Table 34, the resistance of a cable with a 70 mm2 copper conductor and an operating temperature of 75° is 0.327 Ω/km, or 0.000327 Ω/m.

Step 3: Determine cable reactance

The reactance for single core cables depends on the cable type and separation of the cables.

Using Table 30 (refer to Appendix 2 below) we can find the reactance at 50 Hz.

 

Our cables are in a trefoil arrangement, therefore from Column 3 the cable reactance is 0.0893 Ω/km, or 0.0000893 Ω/m.

Step 4: Calculate voltage drop based on power factor and cable operating temperature

We will use Equation 3 to calculate the 3-phase voltage drop. For this we need the phase angle of the load based the given load power factor as follows:

\(\theta = cos^{-1}(0.9)\)

\(\theta = 25.84193276^{\circ} = 0.4510268 \; rads\)

\(sin\theta = 0.43588989\)

Now, we have all parameters needed to calculate the three-phase voltage drop:

\(V_{d3\phi} = 250 \cdot 120[\sqrt{3}(0.000327 \cdot 0.9 + 0.0000893 \cdot 0.43588989)]\)

\(V_{d3\phi} = 17.315 \; V\)

The voltage drop as a percentage of the supply voltage is 17.315 / 400 V, or 4.33%.

Appendices

Appendix 1 – Table 34 with relevant value highlighted in red

processed 6cc4e453 188b 4b25 aea5 2a03877a3f03 EOEkUbgt - Voltage Drop Calculation Method with Examples

Appendix 2 – Table 30 with relevant value highlighted in red

processed 5f519956 9564 484f 8e11 98880fa95075 vaa3zRKp - Voltage Drop Calculation Method with Examples
케이블 프로 웹

클라우드에서 케이블 크기 조정 및 최대 수요 소프트웨어. 설치 없이 모든 기기에서 사용 가능.

관련 문서:

AS/NZS 3008을 사용하여 활성, 중성 및 접지 케이블의 크기를 측정하세요. 이 가이드에서는 전류 용량, 전압 강하 및 단락 계산을 예제와 함께 다룹니다.
소형 회로 차단기(MCB)는 전기 회로의 과전류로부터 보호합니다. 이 문서에서는 Z, B, C, K, D와 같은 다양한 장치 곡선으로 표시되는 트립 특성에 따라 MCB를 분류하고 애플리케이션에 적합한 유형을 선택하는 방법에 대한 지침을 제공합니다.
AS/NZS 3000 표준은 부록 C에서 가정용, 상업용 및 산업용 전기 설비의 소켓 콘센트 최대 수요에 대한 다양한 규칙을 제공합니다. 이중 소켓 콘센트와 관련된 계산 예가 제공됩니다.
경제적인 케이블 사이징의 원칙은 사용하기에 안전하고 수명 기간 동안 손실 비용도 최소화할 수 있는 최소 케이블 크기를 선택하는 것입니다.
표준에 따라 도관 크기 및 공간 계수를 계산하는 방정식이 제공됩니다. 도관 크기 계산의 작동 예가 제공됩니다.
전원 케이블에 흐르는 고장 전류로 인해 온도가 급격히 상승합니다. 단락을 견딜 수 있는 최소 도체 크기를 계산하는 단열 방정식에 대해 설명합니다.