0

장바구니

0
소계: AUD0
장바구니에 제품이 없습니다.

접지 오류 루프 임피던스 이해

접지 오류 루프 임피던스 이해

Ensuring safety through the operation of protection within an adequate time

다운로드:

소개

The purpose of this article is to provide a better understanding of Fault Loop Impedance, also referred to as Earth Fault Loop Impedance so that the requirements of AS/NZS 3000 Wiring Rules for safety, design, installation and testing of electrical installation are met.

You can calculate Fault Loop Impedance by hand or using software. Cable Pro Web software can accurately calculate Fault Loop Impedance.

This document provides:

  1. The theoretical background behind fault loop impedance which will lead to a better understanding for those required to perform the designs and calculations.
  2. A practical guide to performing the processes and procedures to meet the requirements of the Australian and New Zealand Standard AS/NZS 3000:2018.
  3. Information about how the fault loop impedance is used by the Cable Pro Web software to calculate earth cable size.

Theoretical background behind fault loop impedance

The earth fault loop in an MEN system comprises the following components:

  1. The protective earthing conductor (PE) including the main earthing terminal/connection or bar and MEN connection.
  2. The neutral return path consisting of the neutral conductor (N) between the main neutral terminal and the transformer neutral point.
  3. The path through the transformer winding.
  4. The active conductor (A) as far as the point of the fault.

The earth fault loop is normally regarded as consisting of the following two parts:

  1. Conductors upstream or ‘external’ to the reference point.
  2. Conductors downstream or ‘internal’ to the circuit from the reference point.

Figure 2 shows the earth fault loop for an active-earth short circuit. At the instant of the fault current will flow through the earth fault loop with its current magnitude limited by the total path impedance (Zs) which is obtained from the sum of impedances of the individual elements.

세포 주기의 세포 과정을 설명하는 다이어그램입니다.
Figure 2. Fault loop impedance schematic for an active to earth short-circuit.

Requirements of the Australian Standards

AS/NZS 3000 Wiring Rules applies throughout Australia and New Zealand and is references in whole or in part in legislation in all states of Australia and in New Zealand. Therefore, the design and the installation of all electrical circuits in these regions must meet the minimum requirements of this Standard.

A basic safety requirement stated in AS/NZS 3000 is the protection of people from ‘indirect contact’ with live parts. Automatic disconnection of the power supply is the most common way of satisfying this requirement. However, there is a bit more to it than that.

To comply with the Wiring Rules each circuit in an electrical installation must be designed such that automatic disconnection of the power supply occurs within a specified time when a short-circuit of negligible impedance occurs between the active and protective earth conductor or other exposed conductive part anywhere in the electrical installation.

To fulfil this requirement of AS/NZS 3000 when an active to earth fault occurs, and this is the important bit, the total impedance of the fault loop path (consisting of all conductors, connections and contacts as well as the transformer windings) must be low enough to allow sufficient current to flow to ensure the protective device will operate within the specified time.

Therefore, the actual total earth fault loop impedance (Zs) and maximum allowed fault loop impedance Zmax must be obtained.

Calculating the actual fault loop impedance (Zs)

Total earth fault loop impedance (Zs) is approximately equal to the sum of impedances of all of the circuit components in the fault loop impedance current path shown in Figure 2.

That is the total fault loop impedance is equal to:

Zs = Zint + Zext

The internal impedance (Zint) is calculated as:

Zint = impedance of the active conductors + impedance of the earth conductors

An accurate method that Cable Pro uses of determining impedance of the conductors in the earth fault loop path is to use the resistance and reactance data given in AS/NZS 3008.1 – Electrical Installations – Selection of Cables.

To calculate the external impedance (Zext) the rule from AS/NZS 3000 that at least 80 % of the nominal phase voltage will be available at the position of the protective device is used.

Calculating the maximum allowed fault loop impedance (Zmax)

The actual fault loop impedance (Zs) should be lower than the maximum allowed to ensure the circuit protective device will trip during a fault.

The maximum allowed fault loop impedance (Zmax) is calculated based on the rating of the protective device as follows:

The formula for zmax is shown on a white background in an electrical software.

Where

Uo = Nominal phase voltage.
Ia = Current ensuring automatic operating of the protective device.
Zmax = Maximum earth fault loop impedance.

Ia for circuit breaker is the mean tripping current as follows:

  • Type B = 4 (typical) × rated current
  • Type C = 7.5 (typical) × rated current
  • Type D = 12.5 (typical) × rated current
  • Ia for fuses are appropriate mean values from AS 60269.1.

Note the actual trip multiplier value may vary and in Cable Pro software this value is changed to match the actual protective device setting.

The value of maximum earth fault loop impedance (Zmax) with respect to the actual total impedance (Zs) may be used to determine the appropriate earth cable size (explained below).

How to calculate earth cable size

The earth cable size needs to be sufficient to ensure:

  1. Appropriate earth fault loop impedance (Zs).
  2. Adequate current-carrying capacity for prospective earth fault currents for a time at least equal to the tripping time of the associated circuit protection (adiabatic equation).
  3. Adequate mechanical strength.

The selection of the earth cable size is determined from either:

(a)  Table 5.1 in AS/NZS 3000:2018 which provide conservative earth cable sizes with relation to the largest active cable size (or summation where there are parallel circuits).

(b)  By calculation – this requires the protective device details to be known. When calculating earth cable size then appropriate earth fault loop impedance must be ensured.

Cable Pro Web software performs both (a) or (b). When the protective device details are not entered the program uses the conservative earth cable sizes given in AS/NZS 3000. On the other hand, when the protective information is entered it will use the more accurate calculation methods to determine earth cable size, which is usually smaller than the conservative size. The AS/NZS 3000 Wiring Rules mandate that the Earth Fault Loop Impedance of a circuit within an electrical installation must comply with specific requirements to ensure safety. The actual earth fault loop impedance (Zs) (either measured or calculated) must be less than the maximum permissible (Zmax). The earth conductor size is determined with respect to earth fault loop impedance but also adequate short-circuit performance must be ensured by employing the adiabatic equation method from AS/NZS 3008.1. Cable Pro Web is used to quickly and accurately calculate earth fault loop impedance and earth cable sizes in full compliance with the latest Australian Standards.
케이블 프로 웹

클라우드에서 케이블 크기 조정 및 최대 수요 소프트웨어. 설치 없이 모든 기기에서 사용 가능.

관련 문서:

AS/NZS 3008을 사용하여 활성, 중성 및 접지 케이블의 크기를 측정하세요. 이 가이드에서는 전류 용량, 전압 강하 및 단락 계산을 예제와 함께 다룹니다.
소형 회로 차단기(MCB)는 전기 회로의 과전류로부터 보호합니다. 이 문서에서는 Z, B, C, K, D와 같은 다양한 장치 곡선으로 표시되는 트립 특성에 따라 MCB를 분류하고 애플리케이션에 적합한 유형을 선택하는 방법에 대한 지침을 제공합니다.
AS/NZS 3000 표준은 부록 C에서 가정용, 상업용 및 산업용 전기 설비의 소켓 콘센트 최대 수요에 대한 다양한 규칙을 제공합니다. 이중 소켓 콘센트와 관련된 계산 예가 제공됩니다.
경제적인 케이블 사이징의 원칙은 사용하기에 안전하고 수명 기간 동안 손실 비용도 최소화할 수 있는 최소 케이블 크기를 선택하는 것입니다.
표준에 따라 도관 크기 및 공간 계수를 계산하는 방정식이 제공됩니다. 도관 크기 계산의 작동 예가 제공됩니다.
전원 케이블에 흐르는 고장 전류로 인해 온도가 급격히 상승합니다. 단락을 견딜 수 있는 최소 도체 크기를 계산하는 단열 방정식에 대해 설명합니다.

이 문서를 인쇄하세요:

인쇄
케이블 프로 웹 소프트웨어
케이블 프로 웹

케이블 크기, 최대 수요, LV 네트워크 설계, 보호 조정, 케이블 풀링 및 아크 플래시 계산.

사용처

케이블 프로 웹 클라이언트