土壌抵抗率の代表値

For earthing and grounding systems design
Soil resistivity measurements using Wenner method 1 scaled - Typical Values of Soil Resistivity

Why is accurate soil resistivity data important?

The soil electrical resistivity (soil resistivity) is one of the most important factors and has a significant impact on touch and step voltages which occur during a fault on an earthing/grounding system.

If you intend to perform modelling of an earthing system or safety measurements your design or your assessment will only be as accurate as the soil resistivity data.

Soil resistivity variance

Resistivity varies from less than 1 Ω.m for sea water up to 109 Ω.m for sandstone.

Resistivity varies not only with the type of soil but also with temperature, moisture, mineral content, and compactness. Therefore, resistivity should be measured in the field at the actual site of the installation and the conditions under which it was measured must also be recorded.

When to use typical soil resistivity values

There are a number of reasons depending on the stage of your project.

  1. For preliminary earthing system designs.

Your project which is at tender stage involves a significant earthing component (such as a substation) and actual soil resistivity meausurements have not been performed. In order to estimate the costs of an earthing system you will need to estimate soil resistivity.

  1. To validate your soil resistivity measurements.

If you already have soil resistivity measurements and you want to validate them based on your geotechnical knowledge of the local soil and the conditions.

Typical soil resistivity values

Tables 1-3 provide typical soil resistivity values based on soil types. To use these values for your project you should refer to the geotechnical report or if it is not available then find out the types of soils which are present for the region of your project (there are geological maps available).

In addition Table 4 provides the resistivity of typical surface layer materials used for substations.

Table 1. Range of earth resistivity [ref. 1]

Table 2 – Range of soil resistivity [ref. 2]

Table 3. Geological period and formation [ref. 3]

Table 4. Resistivity of typical surface layer materials in substations

Table 5. Resistivity values for various materials [ref. 4]

参考文献

[1] IEEE Std 80 – IEEE Suide for Safety in AC Substation Grounding

[2] CIGRE TB 95 Guide on the Influence of High Voltage Systems on Metallic Pipelines

[3] IEEE Std 81:2012 – IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Grounding System

[4] AS/NZS 1768-2021 – Lightning Protection

SafeGrid アーシングソフトウェア

規格に準拠した安全な接地システムを簡単に設計できます。

関連記事

経験豊富な電気技術者が、変電所や再生可能エネルギーなどの電力系統のアース/接地に関する規格の参考リストを作成しました。
ソフトウェア・シミュレーションがグリッド・インピーダンス試験をどのように強化し、接地システムの設計と性能評価の精度と効率を向上させるかを理解する。
本レポートでは、ケーブル送電線で接続された変電所の地絡電流解析を正確に行う方法を説明する。まず、単純なケーブル送電線と架空送電線の地絡電流について説明する。次に、ハイブリッドケーブル送電線を含む2つのケーススタディを紹介する。
銅はその優れた電気的特性から好まれることが多く、アルミニウムや亜鉛メッキ鋼は費用対効果から選ばれます。銅被覆鋼板は、コストと性能のバランスを取ることができます。この記事では、さまざまなシナリオに最適なオプションをご紹介します。
この技術ガイドは、電気系統、ローカル WTG と複合接地システムの設計、タッチ電圧とステップ電圧の危険性、土壌の電気抵抗測定、地絡電流、接地システムのソフトウェアモデリング、およびウィンドファームのための接地の検証試験について説明しています。
この記事で説明するように、変電所に砕石や砂利が敷かれる理由は、規格によれば2つある。

この記事を印刷する

プリント

SafeGrid アーシングソフトウェア

画面にソフトウェアとグラフが表示される電気機器。

規格に準拠した安全な接地システムを簡単に設計できます。

で使用されている:

SafeGrid アーシングクライアント