接地棒和棒床的电阻

Equations for calculating earthing rod resistance validated with software
A man is digging a hole in the ground with a shovel.

How earthing rods improve safety

Earthing rods are bare metal stakes driven vertically into the ground installed as standalone or in groups as part of an earthing system. Earthing rods may improve safety by reducing earthing grid resistance and reducing touch voltages when driven into low resistivity soil layers.

 Our article on the Fundamentals of Earthing Design explains more.

How far apart to separate earthing rods

For larger earthing systems multiple rods may be connected in the form of rod beds. The individual rods of rod beds should not be installed too close to one another due to the proximity effect which reduces their efficiency. Figure 1 shows how the fields of rods affects other rods while they are dissipating current into the ground during a fault.

The general rule of thumb is earth rods should be separated by at least their driven length.

电力线示意图。
Figure 1 - Proximity effect between two adjacent earth rods

Should earthing rods be encased in concrete?

IEEE Std. 80 [ref. 1] states that encasing rods in concrete may be effective at improving the performance of buried rods. Our article on Concrete-encased Earthing Rods explains more.

Calculating earthing rod resistance

Equations for calculating resistance of individual rods, groups of bare rods and rods encased in concrete are given below. There is also a free Earth Rods Resistance Calculator. Example calculations are given below and the results are validated with SafeGrid Earthing Software.

Single earthing rod equation

计算单杆电阻的常用公式 [1] 为

11 - Resistance of Earthing Rods and Rod Beds

在哪里?

ρ:the resistivity of the soil (Ω.m)
Lr:length of the rod
d: diameter of the ground rod.

Rods bed equation

The simple equation used to calculate the rods bed resistance is given by Schwarz [ref. 1] as:

A diagram of a chemical equation formula.

在哪里?

ρ: Soil resistivity (Ω.m)
nr: Number of rods
Lr: Length of rod (m)
d: diameter of the rod (mm)
A: Grid area (m2)
K1: coefficients

The coefficient K1 formula was given by Kercel [ref. 2] as:

An example of a mathematical formula related to power and renewables.

Where a is the length of the grid and b is the width of the grid.

Rods bed encased in concrete equation

To reduce the soil resistivity around the rod (thus making it more effective) a low resistivity layer is added around it to increase its effectiveness while lowering the cost of materials. With the inclusion of concrete in equation (1), we get the following equation:
eq4 - Resistance of Earthing Rods and Rod Beds
Equation 4 - Resistance of Earthing Rods and Rod Beds

Where:
ρc: the resistivity of concrete (Ω.m)
Dc: Diameter of the concrete shell (mm)

Example hand calculations and software validation

Example 1 – Rods bed resistance

In this example we calculated the resistance of a 20 m by 10 m meshed grid shown Figure 2 which had 15 rods which are 5 m long buried at 0.5 m and were each separated by 5 m. The soil model is 100 Ω.m uniform.

Note that Equation 2 does not consider the effects of the horizontal connected conductors, which is a drawback of the simple equation approach. Therefore, in the SafeGrid software model the horizontal conductors connecting the tops of the rods together were insulated.

For the rod bed in Figure 2, Equation 2 gives a resistance of 3.19 Ω. SafeGrid software calculates 2.851 Ω for the same rod bed arrangement which is 10.6 % lower.

A diagram of a row of power squares.
Figure 2. Software model of rods bed with insulated horizontal conductors
Figure 3. Software results for rod bed
Figure 3. Software results for rod bed

To examine the proximity effects, we varied the spacing between the 5 m rods from 1m (separation factor = 0.2) up to 10 m (separation factor = 2) and calculated resistance.

Figure 4 shows that the simple rod bed resistance equation captures the proximity effect as confirmed by the SafeGrid software model results. The optimal separation between rods is when the separation distance is equal to the rod length.

Figure 4. Rod bed resistances of bare rods
Figure 4. Rod bed resistances of bare rods

Example 2 – Concrete-encased rod bed resistance

In this example the grid is the same as in Example 1 except the rods are encased in concrete with a shell diameter of 200 mm. and the concrete has resistivity of 30 Ω.m which is lower than the native soil resistivity of 100 Ω.m uniform.

For the rod bed in Figure 5, Equation 4 gives a resistance of 2.96 Ω which is lower than the result in Example 1 without concrete encasing of rods.

SafeGrid software calculates the resistance for the concrete-encased rod bed to be 2.545 Ω.

Figure 5. Software model of concrete-encased rods bed with insulated horizontal conductors
Figure 5. Software model of concrete-encased rods bed with insulated horizontal conductors
A graph illustrating the diverse array of colors representing different electrical power sources, including renewables.
Figure 6. Software results for concrete-encased rod bed

To examine the proximity effects, we varied the spacing between the 5 m rods from 1m (separation factor = 0.2) up to 10 m (separation factor = 2) and calculated resistance.

Figure 7 shows how rod bed resistance varies for concrete-encased grid using the simple equation and using SafeGrid software. Once again, the plot confirms that optimal separation between rods is when the separation distance is equal to the rod length.

Figure 7. Rod bed resistances of concrete-encased rods
Figure 7. Rod bed resistances of concrete-encased rods

建议

The simple equations from IEEE Std. 80 [ref. 1] for rod resistance and rod bend resistance have been extended to include the effects of concrete-encasing of the rods. The simple equations appear to capture the proximity effect for rods reasonably. 

The significant limitations of using the simple equations includes:

  • They can only model simple rod arrays with equal separations.
  • They cannot model the horizontal interconnecting conductors.
  • They are limited to only uniform soil models.

Most soils have a multilayer soil resistivity structure. Importantly, rods should in general be used when the bottom layer resistivity is lower than the top layers and the rods should be sufficiently long to penetrate the low resistivity layers.

The significant advantages to using software to model earthing systems includes:

  • Software can model arbitrary earthing arrangements for multi-layered soils resistivity structures.
  • Software results are more accurate resulting in higher degrees of safety and cost savings due to more economical earthing system installations.

参考资料

[1] ‘IEEE Guide for Safety in AC Substation Grounding.’ IEEE Std. 80-2013.
[2] Kercel, S. W., “Design of switchyard grounding systems using multiple grids” IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no. 3, pp. 1341–1350, Mar. 1981.

SafeGrid 接地软件

轻松设计符合标准的安全接地系统。

相关文章

经验丰富的电气工程师为变电站、可再生能源等电力系统的接地/接地标准创建了这份参考清单。
了解软件模拟如何增强电网阻抗测试,提高接地系统设计和性能评估的准确性和效率。
本报告介绍了如何对电缆输电线路连接的变电站进行准确的接地故障电流分析。首先解释了简单电缆和架空输电线路的接地故障电流。接下来,将介绍两个涉及混合电缆输电线路的案例研究。
铜通常因其卓越的电气性能而备受青睐,而铝和镀锌钢则是出于成本效益的考虑。铜包钢可以在成本和性能之间取得平衡。本文介绍了不同情况下的最佳选择。
该技术指南介绍了电气系统、本地风电机组和组合接地系统设计、触电和跨步电压危险、土壤电阻率测量、接地故障电流、接地系统软件建模以及风电场接地验证测试。
根据标准,在变电站内铺设碎石或砾石有两个原因,本文将对此进行说明。

打印本文:

打印

SafeGrid 接地软件

带软件的电子设备,屏幕上有图表。

轻松设计符合标准的安全接地系统。

用于:

安全电网接地客户端