This Cable Sizing Calculator can calculate minimum active, neutral, and earth cable sizes in compliance with the international standard IEC 60364-5-52. It covers all cable types, installation methods, and correction factors in the standards.
This cable sizing standard applies to circuits up to 1,000 V AC or 1,500 V DC.
The calculator follows the cable sizing procedure outlined in IEC Standard 60364-5-52, which is discussed below in detail.
Assumed conditions:
The minimum size of a low-voltage power cable is determined for a particular installation based on its ability to satisfy current-carrying capacity, voltage drop, and short-circuit performance/rating.
The minimum cable size will be the smallest cable that satisfies the three requirements.
⚠️There is also a minimum cable conductor size to meet mechanical strength requirements.
Current carrying capacity, often called ampacity, is the maximum amount of electric current a cable can safely conduct without exceeding its temperature rating. This limit is determined by the cable's conductor material, insulation type, installation method, ambient temperature, and external factors. Constant constant current (100 % load factor) and constant ambient conditions are assumed.
ℹ️ The current-carrying capacity dictates the active cable size for large load currents.
Voltage drop is the reduction in voltage that occurs as current travels through a cable due to the conductor's inherent impedance. This drop is influenced by factors such as the phases of the supply, the length of the cable, the cross-sectional area, the material, the operating temperature of the conductor, the amount of current flowing, and the power factor of the load it supplies.
ℹ️ The voltage drop dictates the active cable size for long route lengths.
Short circuit rating is the maximum current a cable can safely carry for a very short duration during a fault condition, such as a short circuit, without sustaining damage. The minimum cable size to withstand the short-circuit current is determined based on the actual short-circuit current and the specified period (fault clearing time of the protection obtained from the time-current curve).
ℹ️ The short circuit rating (rarely) dictates the active size for short cable runs carrying a small load current and where the supply’s fault level is high.
Conductors must have sufficient mechanical integrity to withstand handling, installation stresses, and environmental conditions without sustaining damage.
Table 52.2 specifies the minimum cross-sectional area of conductors.
A protective device’s primary function is to protect cables from thermal damage due to overload and/or short circuits. Below is the image showing the damage caused by an improperly coordinated circuit protective device and power cables.
The required coordination between the cables and the circuit protection is shown in the figure and explained in the table below.
The following parameters are defined:
Requirements | Notes | |
---|---|---|
ZONE 'A' | The protective device (PD) rating (IN) must be ≥ design current (IB) and ≤ current-carrying capacity (IZ) of the cable. | ℹ️ The rating of fuses must not exceed 0.9IZ. |
ZONE 'B' | The protective device's conventional tripping time (I2) must be ≤ 1.45IZ for circuit breakers and 1.6IZ for fuses. | ℹ️ Standards mandate circuit breakers trip below 1.45IN, ensuring all breakers and fuses comply. |
ZONE 'C' | The protective device fault breaking capacity (ISCB) must be ≥ ISC. | ℹ️ If the overcurrent device only provides fault protection, IN may exceed IZ, and I2 may exceed 1.45 IZ. |
The current carried by a power cable system heats it. The conductor temperature is limited to avoid overheating the adjacent insulation layers.
The temperature limits of insulated cables, such as Thermoplastic PVC (up to 70 °C continuous, 160 °C short circuit), XLPE (up to 90 °C continuous, 250 °C short circuit), Mineral with Thermoplastic PVC Insulation (up to 70 °C continuous, 250 °C short circuit), and Mineral Bare (up to 105 °C continuous, 250 °C short circuit), are crucial for ensuring safety, performance, longevity, and regulatory compliance.
The maximum operating temperature of cable insulation determines a cable’s current-carrying capacity by setting the maximum allowable temperature rise during operation. The table below provides the temperature limits of cable conductors of common cable insulation types.
⚠️ The current carry capacity tables of IEC 60364-5-52 are based on the ‘maximum permissible conductor temperatures' given in Table 52.1.
The international standard IEC 60364-5-52 provides correction factors in Tables B.52.14 to B.52.21.
Refer to these tables for a complete set of correction factors from IEC 60364-5-52.
It’s simple to use correction factors:
Cable sizing calculators may include all relevant correction factors from IEC 60364-5-52
Excessive voltage drop can cause equipment malfunction and failures. Therefore, the standards dictate maximum permissible voltage drop limits. Voltage drop often significantly impacts the minimum cable size and must be calculated accurately.
✅ Accurate voltage drop calculations will result in smaller cable sizes.
Accurately calculating voltage drops results in lower voltage drops, which leads to smaller cable sizes and saves money. The accurate voltage drop equation for three-phase systems is shown below.
ℹ️ For DC voltage drop calculations, the value for reactance X is zero.
The voltage drop between the point of supply for the low-voltage electrical installation and any point in that installation must not exceed a percentage of the nominal voltage of the point of supply, as given in Table G.52.1 (summarised below).
Type of installation | Lighting | Other uses |
---|---|---|
Low-voltage installations supplied directly from a public low-voltage distribution system | 3 % | 5 % |
Low-voltage installation supplied from private LV supply | 6 % | 8 % |
When the cable system length exceeds 100 m, these voltage drop limits may be increased by up to 0.005 % per metre beyond 100 m, without this supplement being greater than 0.5 %.
A greater voltage drop may be accepted for motors or other equipment with high inrush currents during starting periods.
In an unbalanced system, current will be flowing through the neutral conductor as illustrated by the phasor diagram in the figure below:
There are two ways of dealing with voltage drop for unbalanced three-phase circuits:
Where: | Voltage drop calculation method | |
---|---|---|
1 | Out-of-balance conditions are intermittent | Assume balanced three-phase load conditions and use the heaviest loaded phase current. |
2 | Out-of-balance conditions are consistent | Calculate the voltage drop on a single-phase basis by summing the voltage drop in the heaviest loaded phase and neutral. |
Running conductors in parallel is a standard method of increasing a circuit's current-carrying capacity without resorting to excessively large conductors. This technique involves using two or more conductors in parallel to share the electrical load, but it requires careful consideration to ensure safety, efficiency, and compliance with standards.
Using multiple smaller conductors in parallel significantly boosts the circuit's overall current-carrying capacity. Smaller conductors are easier to install, route through conduit, and navigate around obstacles. Parallel conductors provide redundancy; if one conductor fails, the others can continue to carry the load, albeit at a reduced capacity.
⚠️ Parallel conductors require more cables and installation costs than larger or fewer parallel cables.
To avoid overheating one or more parallel cables, it is essential to ensure that the grouping of cables does not affect the cooling of each parallel cable or group and that there is equal load current sharing between them. This is achieved as follows:
ℹ️ IEC 60364-5-52 requires that parallel sets of cables must have a minimum size of 50 mm2 for copper and 70 mm2 for aluminium conductors.
Proper phase arrangements of multiple single-core cables of multi-phase systems are essential for ensuring balanced load current sharing. The figure below from the standard AS/NZS 3008.1 references the optimal phase arrangements for up to four parallel circuits.
The neutral conductor in IEC 60364-5-52 installations is intended to carry current under normal conditions and must be sized appropriately for the system and load conditions.
Single-phase or multi-phase circuits with phase conductors up to and including 16 mm² copper or 25 mm² aluminium require the neutral conductor to be the same size as the phase conductor.
For multi-phase circuits with phase conductors larger than 16 mm² copper or 25 mm² aluminium, the neutral conductor may be smaller than the phase conductors if the maximum expected neutral current, including any harmonic components, does not exceed the current-carrying capacity of the neutral conductor, and the neutral is protected against overcurrent. The minimum neutral size in this case is 16 mm² copper or 25 mm² aluminium.
⚠️ When there are substantial harmonics, the neutral conductor size may need to be larger than the active conductors. In the case of a multi-core cable, the neutral currents may dictate the active size.
Where there are substantial third harmonic currents (typically when the third harmonic current exceeds 33% of the phase current), the neutral conductor must be at least the same size as the phase conductor, as the neutral current can exceed the phase current in these conditions.
For circuits feeding predominantly balanced multi-phase loads, the neutral conductor must be capable of carrying the maximum out-of-balance current, including any harmonic component, and may be smaller than the phase conductors if this requirement is satisfied.
Summary Table:
Type of Circuit | Neutral Conductor Size Requirement |
---|---|
Single-phase or multi-phase | Neutral size not less than the phase conductor size (if phase ≤16 mm² Cu). |
Multi-phase, balanced loads | Neutral may be smaller than the phase conductor (if phase >16 mm² Cu), provided it carries the maximum out-of-balance current. |
Multi-phase, harmonic-rich loads | Neutral size not less than the phase conductor size (if substantial third harmonics present). |
In low-voltage electrical installations, the protective earth (PE) conductor ensures safety by providing a low-impedance path for fault currents, enabling protective devices to operate promptly. IEC 60364-5-54 specifies requirements for sizing PE conductors to handle thermal and mechanical stresses during faults.
The PE conductor must satisfy three criteria:
PE conductor size is determined by the phase conductor’s CSA (copper or aluminium):
Phase Conductor Size (Sph) | Minimum PE Conductor Size (Cu/Al) |
---|---|
Sph ≤ 16 mm² | Sph |
16 < Sph ≤ 35 mm² | 16 mm² (Cu) / 25 mm² (Al) |
Sph > 35 mm² | Sph/2 |
Notes: